What the 1001 alarm means

The TSINO servo drive for the affected axis detected output current above the power-stage limit and shut down to protect the IGBT module. This is one of the faults our repair team handles on EFORT EC2-S controller + TSINO drives systems — the cause is usually identifiable within the first on-site inspection.

Most common causes

  • Motor power cable shorted phase-to-phase or to ground
  • Motor winding insulation failure
  • Damaged drive power module
  • Oil or coolant inside the motor connector
  • Acceleration far beyond the mechanical capability
Field note: the first item on this list is what we find most often on real machines. Check it before you go deeper.

Step-by-step field fix

  1. Power off, let the DC bus discharge, then megger the motor phases to ground
  2. Disconnect the motor and power the drive alone — a repeat 1001 means a dead power stage
  3. Dry and clean contaminated connectors
  4. Check the cable for crush points in the dress pack
  5. Replace the failed part and re-test with a slow jog
Safety first: never bypass safety circuits or force contactors closed. If the alarm involves E-stop chains, brakes or drive power, and you are not a trained robot technician, contact a professional — wrong moves here can cost you a robot or an injury.

Still stuck? Get an engineer on the phone — right now

Tell us the alarm code, the robot model and what was happening when the alarm came up. Our engineers run these diagnostics every day, and remote diagnosis by phone or video call is free.

Get a Free Remote Diagnosis See Repair Services

Hotline: +86-20-39029800 · WhatsApp: +86-188-1886-2860

Other brands: we also keep field-fix libraries for JAKA · AUBO · ROKAE and more — see the complete alarm code hub.

Frequently asked questions

QWhat does the EFORT 1001 alarm mean?

The TSINO servo drive for the affected axis detected output current above the power-stage limit and shut down to protect the IGBT module. In field practice it belongs to the drive & power stage family of faults.

QCan I clear a EFORT 1001 alarm myself?

Sometimes. Work through the step-by-step checks on this page — the first listed cause is what we find most often in the field. If the alarm returns after two attempts, or the fault involves power, brakes or safety circuits, stop and call a qualified robot service engineer.

QHow fast can a Henghuan engineer help?

On-site response in the Pearl River Delta within 30 minutes to 3 hours, across mainland China in 1-3 business days, and worldwide within 2-5 business days. Remote diagnosis by phone/WhatsApp/video is available immediately.

Written by the Henghuan Robotics repair team from field service experience. Alarm descriptions are our own summary for troubleshooting reference and may vary by controller and software version — when in doubt, check your EFORT documentation or contact us. Henghuan is an independent service provider, not affiliated with or endorsed by EFORT.